Quick Start Guide
FCIM-20009-EN Rev. 0
March 2023
3
Section 2: XTE3000 – RDM Wiring Connection
XTE3000 – RDM Wiring Connection
a) RDM power by external single phase 110 V to 220 V AC, 50/60 Hz
AC Line connect to pin1 on P2 connector
AC Neutral connect to pin2 on P2 connector
Connect RS485(+) from A4 to pin 3 (RDM+)
Connect RS485(-) from A5 to pin 5 (RDM-)
Connect Shield from STC24 to pin 4 (RDM)
b) RDM power by external 24 V DC
24 V DC(+) connects to pin10 on P2 connector
24 V DC(-) Ground connects to pin2 on P2 connector
Connect RS485(+) from A4 to pin 3 (RDM+)
Connect RS485(-) from A5 to pin 5 (RDM-)
Connect Shield from STC24 to pin 4 (RDM)