16
EN Drive Installation Manual
Figure 12: EN AC Power Wiring Diagram
L1 L2 L3 PE
Wire crimp ferrules are recommended:
If 14 AWG, use panduit #PV14-P47.
If 12 AWG, use Panduit #PV10-P55.
50/60 Hz
90-264 VAC
Note:
L3 is used with the E
N
-214 only.
When cycling power make sure AC
power is off for 5 seconds minimum
before reapplying power.
L1
Tighten screws to 5 lb-in.
L2
L3 GND
J1
L1 L 2 L 3 PE
Front View
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com