EasyManua.ls Logo

Emerson ControlWave EFM 4710A - Page 67

Emerson ControlWave EFM 4710A
306 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CI-ControlWave EFM Installation & Operation / 2-15
SW2-3 set OFF forces the use of Soft Switches as set per factory default (see Section 2.4.4).
For use of user defined Soft Switches, SW2-3 must be set to the ON position. Note: If both
SW2-3 and SW2-8 are set OFF (closed), all communication ports will be set to 9600 bps
operation (8-bits, no parity, 1 stop bit, BSAP Protocol).
SW2-4 set OFF and used in conjunction with the SCM Mode switch will cause the
ControlWave EFM to perform a Core Updump (see Section 3.6).
SW2-6 set ON will enable the user to perform a remote download of System Firmware (see
Section 2.4.2.3).
SW2-5 set OFF forces the ControlWave EFM to reinitialize SRAM when the unit recovers
from a low power or power outage condition. When set ON, the contents of SRAM will be
retained and utilized when the system restarts. Note: If the Battery is removed from
the CPU Module (CPU removed) CPU should not be installed (and power applied)
before one minute has passed unless SW2-5 on the CPU has been set OFF.
SW2-8 set OFF prevents the ‘Boot Project’ from running and places the unit into diagnostic
mode. SW2-8 must be set OFF to run the WINDIAG program resident on the local PC (see
Section 3.5). When SW2-8 has been set ON, diagnostics is disabled. SW2-8 must be set to
the ON position for normal system operation, i.e. for the Boot project to run. Note: If both
SW2-3 and SW2-8 are set OFF (closed), all communication ports will be set to 9600 bps
operation (8-bits, no parity, 1 stop bit, BSAP Protocol).
Table 2-6 in Section 2.3.3.3 provides CPU Switch SW3 (COM3) and ECOM Switch SW1
COM5/9 RS-485 communication port settings.
Figure 2-9 - CPU Module Component Identification Diagram