11
Nameplate Information
All important information for identication of the compressor is printed on the nameplate located below the compressor oil pump.
The type of refrigerant used should be stamped on the nameplate by the installer.
The date of production indicates the year and week of production. The year and month of production are also part of the serial number
(Jan. = A, Feb. = B, ... Dec. = L).
Qualified Refrigerants and Oils
Application Range
Figure 3
IMPORTANT
It is essential that the glide of refrigerant blends (primarily R407C) is carefully considered when adjusting pressure and
superheat controls.
Oil recharge values can be taken from Copeland
brand products Selection Software on www.EmersonClimateAsia.com
Qualified Refrigerants R404A, R407A, R407C, R407F, R134a, R507 R22
Copeland
Brand Products
Standard Oil
Emkarate RL 32 3MAF Karamay 32BYMO
Servicing Oil
Emkarate RL 32 3MAF
Mobil EAL Arctic 22 CC
Karamay 32BYMO, Suniso 3GS
Shell 22-12, Texaco Capella WF32
Table 2: Qualied refrigerants and oils for recharging and topping up
To Recharge:
When the compressor is completely empty of oil, the amount of oil to be “recharged” is typically 0.12 litre less than the original oil
charge (oil will already be around the system).
To Top up:
During commissioning, planned maintenance or servicing, add oil so that the compressor oil level is correct.
20K Suction Superheat
20°C Return Gas Temperature