EasyManua.ls Logo

Emerson Copeland 4MF-13X - Wiring Diagrams

Emerson Copeland 4MF-13X
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16 17
Wiring Diagrams
The position of the jumpers in the terminal box and the recommended wiring diagrams are shown in Figures 9 and 10.
Wiring Diagram for Part Winding Motors (AW---)
Part winding motors can be connected direct-on-line or part-winding start.
Part-winding motor:
Y - Y
Code A
Direct-on-line start
Y - Y
Part-winding start
First start step 1-2-3
Y - Y
L1 L2 L3
1(U) 2(V) 3(W)
7(Z) 8(X) 9(Y)
L3L2L1
1(U) 2(V) 3(W)
7(Z) 8(X) 9(Y)
Figure 9
A4 ........ Sensor module K1 ............ Contactor M1
A5 ........ Terminal box compressor K4 ............ Contactor M1 for second part winding
CCH ...... Crankcase heater M2 ........... Fan motor/condenser
F6 ......... Fuse for control circuit M21 ......... Fan motor/condenser
F7 ......... Fuse for control circuit R2 ............ Crankcase heater
F8 ......... Fuse for control circuit Y21 .......... Solenoid valve capacity control 1
F10 ....... Thermal protection switch M2 Y22 .... Solenoid valve capacity control 2
21 2928272625242322 30
in A5
M21 F10 Y21Y22
N/BU
L/BN
-/BK
WH
WH
K1 K4
L1 L2 L3
F6 F7 F8
MODULE COMM
R2
CCH
POWER
24 VAC
INPUT
A4
A5
PE
1(U) 2(V) 3(W)
7(Z) 8(X) 9(Y)
S1 S2
BLACK
WHITE
WHITE
CURRENT
SENSOR
COMPRESSOR
WIRING
HARNESS

Other manuals for Emerson Copeland 4MF-13X