30 31
Capacity Control Position
Capacity control must be tted in the following positions:
• 4M* 50% terminal box side
• 6M* 1st step 33% upper cylinder head
• 6M* 2nd step 66% terminal box side
50%
V.1.18.00
Capacity control position 4M* Capacity control position 6M*
33%
66%
V.1.19.00
HM = high and medium temperature
ML = medium and low temperature
Compressor
Number of
cylinders with
capacity control
Capacity regulation step
Remaining
refrigeration
capacity %
(average values)
Remaining
power input %
(average values)
Figure Nr
0 1 2
Application range
HM ML HM ML
4MA1-22X 2 100% 50% 52 59 5
4MH1-25X 2 100% 50% 52 59 5
4MI1-30X 2 100% 50% 52 59 5
4MJ1-30X 2 100% 50% 52 59 5
4MK1-32X 2 100% 50% 52 59 5
4MF1-13X 2 100% 50% 52 59 6
4ML1-15X 2 100% 50% 52 59 6
4MM1-20X 2 100% 50% 52 59 6
4MT1-22X 2 100% 50% 52 59 6
4MU1-25X 2 100% 50% 52 59 6
6MI1-40X 2 /4 100% 66% 33% 68/34 70/41 5
6MJ1-45X 2 /4 100% 66% 33% 68/34 70/41 5
6MK1-50X 2 /4 100% 66% 33% 68/34 70/41 5
6MM1-30X 2 /4 100% 66% 33% 68/34 70/41 6
6MT1-35X 2 /4 100% 66% 33% 68/34 70/41 6
6MU1-40X 2 /4 100% 66% 33% 68/34 70/41 6
R404A Capacity Control Selection Table