The following parameters need to be changed to control a cooling cabinet or a cold room with a
temperature sensor:
Recommended setting / Comments
Thermostat temp (NTC10K) = 2 = TMT or
Evaporator temp (NTC10K) = 5 = EPT
Compressor
regulation probe
selection
1 = Suction pressure
probe = SUP
Case temperature = 2 = CST
Case temperature
probe selection
Thermostat temperature = 4 = TMT or
Evaporator temperature = 5 = EPT
Setpoint case
temperature
Choose setpoint according to requirements
of cooled goods
Position
differential case
temperature
Setpoint G02 + positive differential G03
results in cut-out value for compressor
Case temperature
lower limit G02
Define limits to avoid wrong operator
settings for G02
Case temperature
upper limit G02
Define limits to avoid wrong operator
settings for G02
In case of probe failure the compressor will
be cycled on time based on G06 & G07
In case of probe failure the compressor will
be cycled on time based on G06 & G07
Table 10: External temperature sensor – Parameters
Please check that the setting for G56 is "NO" (means no Solenoid valve in the liquid line) and no
additional digital inputs are configured (Digital Input DI3; Parameter R07 has to be "not used" =
NU = 0).
Defrost
The XCM-25D is able to control defrost on evaporators. The controller can handle electrical
defrost or natural / fan defrost (select by G17). The defrost probe (G12) provides the XCM-25D
with the information about the temperatures in the evaporator.
The intervals between the defrost cycles are controlled by parameter G23. This can be done by
means of the integrated real time clock or by fixed intervals.
Recommended setting / Comments
Evaporator temp (NTC10K) = 5 = EPT
5 = Evaporator temperature sensor = EPT
0 = Electrical = EL; 1 = Hot gas defrost = IN; 2
= Natural defrost (pulse defrost) = PLS
Interval between
defrost cycles
0 – 120 hours range; adjust to individual
requirements
Maximum duration
of defrost
0 – 255 minutes; adjust to individual
requirements
Duration of pulse
defrost
Defrost
termination
temperature