22
© 2015 Emerson Climate Technologies, Inc.
AE4-1400 R1
Outdoor Ambient 85°F (29°C) 95°F (35°C) 105°F (40°C)
System On-Time (Minutes) 7 14 54
System Off-Time (Minutes) 13 8 6
Number of On/Off Cycles 5 5 4
Table 2
Field Application Test
Recommended Conguration
Component Description
TubingConguration Shock loop
Service Valve "Angled valve" fastened to unit
Suctionmufer Not required
Alternate Conguration
Component Description
TubingConguration Shock loop
Service Valve "Straight through" valve not fastened to unit
Mass/Suctionmufer May be required (Acts as dampening mass)
Table 3
Design Congurations
Table 4 – Refrigerant Charge Limits
Model
Compressor Charge Limit System Charge Limit
Pounds kg Pounds kg
ZP10-31K6 8 3.6 9.6 4.4
ZP34-54K6 10 4.5 12 5.4