Table 2
Field Application Test
Operate the system as it would be operated in an actual eld installation, cycling the
unit on and off for the times indicated at each ambient.
Outdoor Ambient 85°F (29°C) 95°F (35°C) 105°F (40°C)
System On-Time (Minutes) 7 14 54
System Off-Time (Minutes) 13 8 6
Number of On/Off Cycles 5 5 4
Recommended Conguration
Component Description
Tubing Conguration Shock loop
Service Valve “Angled valve” fastened to unit
Suction mufer Not required
Alternate Conguration
Component Description
Tubing Conguration Shock loop
Service Valve “Straight through” valve not fastened to unit
Suction mufer May be required (Acts as dampening mass)
Table 3
K1 *K2 K3 K4 KC
ZR18 25µf/370 volt 30µf/370 volt 35µf/370 volt 30µf/370 volt
ZR23 30µf/370 volt 40µf/370 volt 35µf/370 volt 35µf/370 volt
ZR26 35µf/370 volt 40µf/370 volt 30µf/440 volt
ZR28 35µf/370 volt 45µf/370 volt 35µf/440 volt
ZR34 35µf/440 volt 50µf/370 volt 40µf/370 volt
ZR40 35µf/440 volt 55µf/370 volt 40µf/440 volt
ZR46 40µf/440 volt 60µf/370 volt
ZR49 40µf/440 volt 60µf/370 volt 45µf/440 volt
ZR57 55µf/440 volt 80µf/370 volt 60µf/370 volt
ZR61 55µf/440 volt 80µf/370 volt 60µf/370 volt
Table 4
Recommended Run Capacitors for Field Replacement
of a ZR*K1 or K2 with a ZR*K3, K4, or KC