8
10
Quick Access Menu Browse - Sensors Status and Actual Values
Access Alarm Code (Maximum of 50 record)
Step Action Phenomenon and Description
1
Press “
Enter quick access menu, will display“P1P”(Press “Up” or “Down” to view other sensors
2
Press “
View the actual value of “P1P”
3
Press “
Change to next Sensor code
4
Press “
” + “
Exit (or exit automatically after waiting for 60 seconds)
Sensor Code and Values Descriptions
(“nP”, “noP”, or“nA” mean that the sensor
does not exist; “Err” means that the sensor
fails, out of range, disconnected, or does
not congure correctly)
P1P : suction pressure sensor (only for ZXD unit)
P2t : condensing temperature ((mid-coil) sensor
P2P : pressure sensor (not used)
P3 : discharge line temperature sensor
P4 : PHE vapor inlet temperature sensor
P5 : PHE vapor outlet temperature sensor
P6 : ambient temperature sensor
P7 : temperature sensor (not used)
SH : PHE superheat
oPP : EXV opening step
LLS : the status of liquid line solenoid valve
Std : Condensing temperature setting point
Aoo : The percentage of the analog output
dSo : percentage of the PWM output driving the valve of the Digital Scroll
compressor
Lt : min cold room temperature (may not be available)
Ht : max cold room temperature (may not be available)
HM : Time menu
Step Action Phenomenon and Description
1
Press “
Display “SEC”
2
Press “
Display “A01”
3
Press “
Display alarm code in “A01”
4
Press “
Display “A02”
5
Press “
Display alarm code in “A02”
6
7
Press “
” + “
Exit (or exit automatically after waiting for 15 seconds)