Quick Installation Guide Test of DPI-E, On/Off signals
IG 8000-81-003 Ed 01 February 2020
16
5. Set the multimeter to
sound signals.
6. Test of ‘Closed’ signal:
The multimeter should
give a sound signal when
connecting the multime-
ter to terminal 9 + 10.
7. Operate the hand pump
until the actuator is fully
‘Open’ (spindle moves in).
The sound signal should
turn off.
8. Test of ‘Open’ signal:
The multimeter should
give a sound signal when
connecting the multime-
ter to terminal 7 + 8.
Caution! If any of the sound signals described above fail to appear, please consult the description for
adjustment of the DPI on page 19.
9. Disconnect the multimeter.
10. Leave the actuator in position 'Closed' = actuator spindle is max. out.