Quick Installation Guide Test of DPI-C, analog signals
QIG 8000-81-003 Ed 01 February 2020
18
6. Test of ‘Closed’ signal:
The multimeter should
show 300/1500 Ω when
connecting the multime-
ter to terminal 7 + 9.
Operate the hand pump
until the actuator is fully
‘Open’ (spindle moves in).
7. Test of ‘Open’ signal:
The multimeter should
1400/7000 Ω when con-
necting the multimeter to
terminal 7 + 9. All values
are +/- 50 Ω.
Caution! If any of the sound signals described above fail to appear, please consult the description for
adjustment of the DPI on page 19.
8. Disconnect the multimeter.
9. Leave the actuator in position 'closed' = actuator spindle is max. out.