1592026260 IEV22-24D GB r.1.0 21.02.2019 IEV 20/60
Multipolar connector
Terminal
Description
1
AC supply: 24Vac
DC supply: Reference “+“ 24 Vdc
2
Analogue input 1 (NTC, PTC, PT1000)
3
Analogue input 2 (NTC, PTC, PT1000)
4
Analogue input 3 (NTC, PTC, PT1000, 0 - 5V, 4 - 20 mA)
5
Analogue input 4 (NTC, PTC, PT1000, 0 - 5V, 4 - 20 mA)
6
LAN Connection (+ terminal) to connect to IC200 EVO series
7
AC supply: 24Vac
DC supply: Reference “-“ 24 Vdc
8
Analogue inputs common line
9
Voltage output +12Vdc (to connect current trasducers)
10
Ground (to connect rathiometric probe)
11
Voltage output +5Vdc (to connect rathiometric probe)
12
LAN Connection (- terminal) to connect to IC200 EVO series
Digital input connector
Terminal
Type
Description
28
DI1
Digital input 1
29
C
Common digital inputs
30
DI2
Digital input 2
31
DI3
Digital input 3
32
C
Common digital inputs
33
DI4
Digital input 4
Serial output RS485 and relays output
Terminal
Type
Description
17
RS485 +
RS485 Connection (+ terminal)
18
RS485 -
RS485 Connection (- terminal)
19
C
Common relay 1
20
RL1
Relay 1
21
C
Common relay 2
22
RL2
Relay 2

Related product manuals