EasyManua.ls Logo

Emerson Dixell XW60LH - Alarm Signals and Recovery; Alarm Signal Messages and Causes; Alarm Recovery Procedures; Other Alarm and Input Handling

Emerson Dixell XW60LH
6 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Message
Cause
Outputs
EA
External alarm
Output unchanged.
CA
Serious external alarm (i1F=bAL)
All outputs OFF.
CA
Pressure switch alarm (i1F=PAL)
All outputs OFF
rtC Real time clock alarm
Alarm output ON; Other outputs unchanged;
Defrosts according to par. idF Set real time clock
has to be set.
rtF Real time clock board failure
Alarm output ON; Other outputs unchanged;
Defrosts according to par. idF. Contact the
service.
14.1 SILENCING BUZZER / ALARM RELAY OUTPUT
- tbA=Y: the buzzer and the relay are is silenced by pressing any key.
- tbA=n: only the buzzer is silenced while the alarm relay is on until the alarm condition
recovers.
14.2 ALARM RECOVERY
Probe alarms P1, P2, P3 and P4 start some seconds after the fault in the related probe; they
automatically stop some seconds after the probe restarts normal operation. Check connections
before replacing the probe.
Temperature alarms HA, LA, HA2 and LA2 automatically stop as soon as the temperature returns to
normal values.
Alarms EA and CA (with i1F=bAL) recover as soon as the digital input is disabled.
Alarm CA (with i1F=PAL) recovers only by switching off and on the instrument.
14.3 OTHER MESSAGES
on
Keyboard enabled after automatic lock.
LOC
Keyboard automatically locked
Pon
Keyboard unlocked.
PoF
Keyboard locked
noP
In programming mode: none parameter is present in Pr1
On the display or in dP2, dP3, dP4: the selected probe is nor enabled
15. TECHNICAL DATA
Housing: self extinguishing ABS
Case: facia 38x185 mm; depth [XW60LH: 76mm],
Mounting: panel mounting in a 150x31 mm panel cut-out with the 2 metal brackets supplied
Protection: IP20
Frontal protection: IP65
Connections: screw terminal block
2.5 mm
2
heat-resistant wiring and 6.3mm Faston
Power supply: 230Vac or. 120Vac or 24Vac
± 10%
Power absorption: 9VA max
Display: 3 digits, white LED, 14.2 mm high
Inputs: Up to 4 NTC or PTC probes
Digital inputs: 2 free voltage
Relay outputs for XW60LH models: Total current on loads MAX. 20A
Compressor: relay SPST 20(8) A, 250Vac
Light: relay SPST 8 or 16(3) A, 250Vac
Fans: relay SPST 8(3) A, 250Vac
Defrost: relay SPST 8(3) A, 250Vac
Other output: buzzer
Serial output: TTL standard
Communication protocol: Modbus - RTU
Data storing: on the non-volatile memory (EEPROM)
Internal clock back-up: 24 hours (only for model with RTC)
Kind of action: 1B
Pollution degree: 2
Software class: A
Rated impulsive voltage: 2500V
Over voltage Category: II
Operating temperature: 0 to 60 °C (32 to 140°F)
Storage temperature: -30 to 85°C (-22 to 185°F).
Relative humidity: 20 to 85% (not condensing)
Measuring and regulation range:
NTC probe: -40 to 110°C (-40 to 230°F)
PTC probe: -50 to 150°C (-58 to 302°F)
Resolution: 0.C or 1°C or 1°F (selectable)
Accuracy (ambient temp. 25°C): ±0.7°C ±1 digit
16. CONNECTIONS
16.1 XW60LH
Supply: 120Vac or 24Vac: connect to terminals 11-12
The X-REP output is optional
The light relay can be also 16(5)A according to the model
17. DEFAULT SETTING VALUES
Label
Name
Range
°C/°F
Level
Set
Set point
LS÷US
-5.0
- - -
rtc*
Real time clock menu
-
-
Pr1
Hy
Differential
0,1÷25.5°C/ 1÷ 255°F
2.0
Pr1
LS
Minimum set point
-50°C÷SET/-58°F÷SET
-50.0
Pr2
US
Maximum set point
SET÷110°C/ SET ÷ 230°F
110
Pr2
Ot
Thermostat probe calibration
-12÷12°C /-120÷120°F
0.0
Pr1
P2P
Evaporator probe presence
n=not present; Y=pres.
Y
Pr1
Label
Name
Range
°C/°F
Level
OE
Evaporator probe calibration
-12÷12°C /-120÷120°F
0.0
Pr2
P3P
Third probe presence
n=not present; Y=pres.
n
Pr2
O3
Third probe calibration
-12÷12°C /-120÷120°F
0
Pr2
P4P
Fourth probe presence
n=not present; Y=pres.
n
Pr2
O4
Fourth probe calibration
-12÷12°C /-120÷120°F
0
Pr2
OdS
Outputs delay at start up
0÷255 min
0
Pr2
AC
Anti-short cycle delay
0 ÷ 50 min
1
Pr1
Ac1
Second compressor start delay
0÷255s
5
Pr2
rtr
P1-P2 percentage for regulation
0 ÷ 100 (100=P1 , 0=P2)
100
Pr2
CCt
Continuous cycle duration
0.0÷24.0h
0.0
Pr2
CCS
Set point for continuous cycle
(-55.0÷150,0°C) (-67÷302°F)
-5
Pr2
COn
Compressor ON time with faulty probe
0 ÷ 255 min
15
Pr2
COF
Compressor OFF time with faulty probe
0 ÷ 255 min
30
Pr2
CF
Temperature measurement unit
°C ÷ °F
°C
Pr2
rES
Resolution
in=integer; dE= dec.point
dE
Pr1
Lod
Probe displayed
P1;P2
P1
Pr2
rEd
2
X-REP display
P1 P2 P3 P4 SEt dtr
P1
Pr2
dLy
Display temperature delay
0 ÷ 20.0 min (10 sec.)
0.0
Pr2
dtr
P1-P2 percentage for display
1 ÷ 99
50
Pr2
EdF*
Kind of interval for defrost
rtc ÷in
in
Pr2
tdF
Defrost type
EL=el. heater; in= hot gas
EL
Pr1
dFP
Probe selection for defrost termination
nP; P1; P2; P3; P4
P2
Pr2
dtE
Defrost termination temperature
-50 ÷ 50 °C
8
Pr1
IdF
Interval between defrost cycles
1 ÷ 120 ore
6
Pr1
MdF
(Maximum) length for defrost
0 ÷ 255 min
30
Pr1
dSd
Start defrost delay
0÷99min
0
Pr2
dFd
Displaying during defrost
rt, it, SEt, DEF
it
Pr2
dAd
MAX display delay after defrost
0 ÷ 255 min
30
Pr2
Fdt
Draining time
0÷120 min
0
Pr2
dPo
First defrost after start-up
n=after IdF; y=immed.
n
Pr2
dAF
Defrost delay after fast freezing
0 ÷ 23h e 50’
0.0
Pr2
Fnc
Fan operating mode
C-n, o-n, C-y, o-Y
o-n
Pr1
Fnd
Fan delay after defrost
0÷255min
10
Pr1
Fct
Differential of temperature for forced activation
of fans
0÷50°C
10 Pr2
FSt
Fan stop temperature
-50÷50°C/-58÷122°F
2
Pr1
Fon
Fan on time with compressor off
0÷15 (min.)
0
Pr2
FoF
Fan off time with compressor off
0÷15 (min.)
0
Pr2
FAP
Probe selection for fan management
nP; P1; P2; P3; P4
P2
Pr2
ACH
Kind of action for auxiliary relay
CL; Ht
cL
Pr2
SAA
Set Point for auxiliary relay
-50,0÷110°C / -58÷230°F
0,0
Pr2
SHy
Differential for auxiliary relay
0,1÷25.5°C/ 1÷ 255°F
2,0
Pr2
ArP
Probe selection for auxiliary relay
nP / P1 / P2 / P3/P4
nP
Pr2
Sdd
Auxiliary relay operating during defrost
n÷y
n
Pr2
ALP
Alarm probe selection
nP; P1; P2; P3; P4
P1
Pr2
ALc
Temperat. alarms configuration
rE= related to set;
Ab = absolute
Ab Pr2
ALU
MAXIMUM temperature alarm
Set÷110.0°C; Set÷230°F
110,0
Pr1
ALL
Minimum temperature alarm
-50.0°C÷Set/ -58°F÷Set
-50,0
Pr1
AFH
Differential for temperat. alarm recovery
(0,1°C÷25,5°C) (1°F÷45°F)
2,0
Pr2
ALd
Temperature alarm delay
0 ÷ 255 min
15
Pr2
dAO
Delay of temperature alarm at start up
0 ÷ 23h e 50’
1,3
Pr2
AP2
Probe for temperat. alarm of condenser
nP; P1; P2; P3; P4
P4
Pr2
AL2
Condenser for low temperat. alarm
(-55 ÷ 150°C) (-67÷ 302°F)
-40
Pr2
AU2
Condenser for high temperat. alarm
(-55 ÷ 150°C) (-67÷ 302°F)
110
Pr2
AH2
Differ. for condenser temp. alar. recovery
[0,1°C ÷ 25,5°C] [1°F ÷ 45°F]
5
Pr2
Ad2
Condenser temperature alarm delay
0 ÷ 254 (min.) , 255=nU
15
Pr2
dA2
Delay of cond. temper. alarm at start up
0.0 ÷ 23h 50’
1,3
Pr2
bLL
Compr. off for condenser low temperature alarm
n(0) - Y(1)
n
Pr2
AC2
Compr. off for condenser high temperature
alarm
n(0) - Y(1)
n Pr2
tbA
Alarm relay disabling
n=no; y=yes
y
Pr2
oA3
Fourth relay configuration
ALr = alarm; dEF = do not select it;
Lig =Light; AUS =AUX; onF=always
on; Fan= do not select it; db =
neutral
zone; cP2 = second compressor; dF2
= do not select it; HES = night blind
Lig Pr2
AoP
Alarm relay polarity (oA3=ALr)
oP; cL
cL
Pr2
i1P
Digital input polarity (13-14)
oP=opening;CL=closing
cL
Pr1
i1F
Digital input 1 configuration (13-14)
EAL, bAL, PAL, dor; dEF; Htr, AUS
dor
Pr1
did
Digital input alarm delay (13-14)
0÷255min
15
Pr1
i2P
Digital input polarity (13-19)
oP=opening;CL=closing
cL
Pr2
i2F
Digital input configuration (13-19)
EAL, bAL, PAL, dor; dEF; Htr, AUS
EAL
Pr2
d2d
Digital input alarm delay (13-19)
0÷255min
5
Pr2
Nps
Number of activation of pressure switch
0 ÷15
15
Pr2
odc
Compress and fan status when open door
no; Fan; CPr; F_C
F-c
Pr2
rrd
Regulation restart with door open alarm
n – Y
y
Pr2
HES
Differential for Energy Saving
(-30°C÷30°C) (-54°F÷54°F)
0
Pr2
Hur*
Current hour
0 ÷ 23
-
rtc
Min*
Current minute
0 ÷ 59
-
rtc
dAY*
Current day
Sun ÷ SAt
-
rtc
Hd1*
First weekly holiday
Sun÷ SAt nu
nu
rtc
Hd2*
Second weekly holiday
Sun÷ SAt nu
nu
rtc
ILE*
Energy Saving cycle start during workdays
0 ÷ 23h 50 min.
0
rtc
dLE*
Energy Saving cycle length during workdays
0 ÷ 24h 00 min.
0
rtc
ISE*
Energy Saving cycle start on holidays
0 ÷ 23h 50 min.
0
rtc
dSE*
Energy Saving cycle length on holidays
0 ÷ 24h 00 min.
0
rtc
Ld1*
1
st
workdays defrost start
0 ÷ 23h 50 min. - nu
6.0
rtc
Ld2*
2
nd
workdays defrost start
0 ÷ 23h 50 min. - nu
13.0
rtc
Ld3*
3
rd
workdays defrost start
0 ÷ 23h 50 min. - nu
21.0
rtc
Ld4*
4
th
workdays defrost start
0 ÷ 23h 50 min. - nu
0.0
rtc
Ld5*
5
th
workdays defrost start
0 ÷ 23h 50 min. - nu
0.0
rtc
Ld6*
6
th
workdays defrost start
0 ÷ 23h 50 min. - nu
0.0
rtc
Sd1*
1
st
holiday defrost start
0 ÷ 23h 50 min. - nu
6.0
rtc
Sd2*
2
nd
holiday defrost start
0 ÷ 23h 50 min. - nu
13.0
rtc
Sd3*
3
rd
holiday defrost start
0 ÷ 23h 50 min. - nu
21.0
rtc
Sd4*
4
th
holiday defrost start
0 ÷ 23h 50 min. - nu
0.0
rtc
Sd5*
5
th
holiday defrost start
0 ÷ 23h 50 min. - nu
0.0
rtc
Sd6*
6
th
holiday defrost start
0 ÷ 23h 50 min. - nu
0.0
rtc
Adr
Serial address
1÷247
1
Pr2
PbC
Kind of probe
Ptc; ntc
ntc
Pr2
onF
on/off key enabling
nu, oFF; ES
oFF
Pr2
1592036000 XW60LH GB r1.0 18.03.2015 XW60LH 5/6