Serious external alarm (i1F=bAL)
Pressure switch alarm (i1F=PAL)
rtC Real time clock alarm
Alarm output ON; Other outputs unchanged;
Defrosts according to par. idF Set real time clock
rtF Real time clock board failure
Alarm output ON; Other outputs unchanged;
Defrosts according to par. idF. Contact the
14.1 SILENCING BUZZER / ALARM RELAY OUTPUT
- tbA=Y: the buzzer and the relay are is silenced by pressing any key.
- tbA=n: only the buzzer is silenced while the alarm relay is on until the alarm condition
recovers.
14.2 ALARM RECOVERY
Probe alarms P1, P2, P3 and P4 start some seconds after the fault in the related probe; they
automatically stop some seconds after the probe restarts normal operation. Check connections
before replacing the probe.
Temperature alarms HA, LA, HA2 and LA2 automatically stop as soon as the temperature returns to
normal values.
Alarms EA and CA (with i1F=bAL) recover as soon as the digital input is disabled.
Alarm CA (with i1F=PAL) recovers only by switching off and on the instrument.
14.3 OTHER MESSAGES
Keyboard enabled after automatic lock.
Keyboard automatically locked
In programming mode: none parameter is present in Pr1
On the display or in dP2, dP3, dP4: the selected probe is nor enabled
15. TECHNICAL DATA
Housing: self extinguishing ABS
Case: facia 38x185 mm; depth [XW60LH: 76mm],
Mounting: panel mounting in a 150x31 mm panel cut-out with the 2 metal brackets supplied
Protection: IP20
Frontal protection: IP65
Connections: screw terminal block
≤ 2.5 mm
2
heat-resistant wiring and 6.3mm Faston
Power supply: 230Vac or. 120Vac or 24Vac
± 10%
Power absorption: 9VA max
Display: 3 digits, white LED, 14.2 mm high
Inputs: Up to 4 NTC or PTC probes
Digital inputs: 2 free voltage
Relay outputs for XW60LH models: Total current on loads MAX. 20A
Compressor: relay SPST 20(8) A, 250Vac
Light: relay SPST 8 or 16(3) A, 250Vac
Fans: relay SPST 8(3) A, 250Vac
Defrost: relay SPST 8(3) A, 250Vac
Other output: buzzer
Serial output: TTL standard
Communication protocol: Modbus - RTU
Data storing: on the non-volatile memory (EEPROM)
Internal clock back-up: 24 hours (only for model with RTC)
Kind of action: 1B
Pollution degree: 2
Software class: A
Rated impulsive voltage: 2500V
Over voltage Category: II
Operating temperature: 0 to 60 °C (32 to 140°F)
Storage temperature: -30 to 85°C (-22 to 185°F).
Relative humidity: 20 to 85% (not condensing)
Measuring and regulation range:
NTC probe: -40 to 110°C (-40 to 230°F)
PTC probe: -50 to 150°C (-58 to 302°F)
Resolution: 0.1°C or 1°C or 1°F (selectable)
Accuracy (ambient temp. 25°C): ±0.7°C ±1 digit
16. CONNECTIONS
16.1 XW60LH
Supply: 120Vac or 24Vac: connect to terminals 11-12
The X-REP output is optional
The light relay can be also 16(5)A according to the model
17. DEFAULT SETTING VALUES
Thermostat probe calibration
Evaporator probe presence
Evaporator probe calibration
Outputs delay at start up
Second compressor start delay
P1-P2 percentage for regulation
Continuous cycle duration
Set point for continuous cycle
(-55.0÷150,0°C) (-67÷302°F)
Compressor ON time with faulty probe
Compressor OFF time with faulty probe
Temperature measurement unit
in=integer; dE= dec.point
P1 – P2 – P3 – P4 – SEt – dtr
Display temperature delay
P1-P2 percentage for display
Kind of interval for defrost
EL=el. heater; in= hot gas
Probe selection for defrost termination
Defrost termination temperature
Interval between defrost cycles
(Maximum) length for defrost
Displaying during defrost
MAX display delay after defrost
First defrost after start-up
Defrost delay after fast freezing
Differential of temperature for forced activation
of fans
Fan on time with compressor off
Fan off time with compressor off
Probe selection for fan management
Kind of action for auxiliary relay
Set Point for auxiliary relay
Differential for auxiliary relay
Probe selection for auxiliary relay
Auxiliary relay operating during defrost
Temperat. alarms configuration
rE= related to set;
Ab = absolute
MAXIMUM temperature alarm
Minimum temperature alarm
Differential for temperat. alarm recovery
(0,1°C÷25,5°C) (1°F÷45°F)
Delay of temperature alarm at start up
Probe for temperat. alarm of condenser
Condenser for low temperat. alarm
(-55 ÷ 150°C) (-67÷ 302°F)
Condenser for high temperat. alarm
(-55 ÷ 150°C) (-67÷ 302°F)
Differ. for condenser temp. alar. recovery
[0,1°C ÷ 25,5°C] [1°F ÷ 45°F]
Condenser temperature alarm delay
Delay of cond. temper. alarm at start up
Compr. off for condenser low temperature alarm
Compr. off for condenser high temperature
alarm
Fourth relay configuration
ALr = alarm; dEF = do not select it;
Lig =Light; AUS =AUX; onF=always
on; Fan= do not select it; db =
neutral
zone; cP2 = second compressor; dF2
= do not select it; HES = night blind
Alarm relay polarity (oA3=ALr)
Digital input polarity (13-14)
Digital input 1 configuration (13-14)
EAL, bAL, PAL, dor; dEF; Htr, AUS
Digital input alarm delay (13-14)
Digital input polarity (13-19)
Digital input configuration (13-19)
EAL, bAL, PAL, dor; dEF; Htr, AUS
Digital input alarm delay (13-19)
Number of activation of pressure switch
Compress and fan status when open door
Regulation restart with door open alarm
Differential for Energy Saving
(-30°C÷30°C) (-54°F÷54°F)
Energy Saving cycle start during workdays
Energy Saving cycle length during workdays
Energy Saving cycle start on holidays
Energy Saving cycle length on holidays
1
st
workdays defrost start
2
nd
workdays defrost start
3
rd
workdays defrost start
4
th
workdays defrost start
5
th
workdays defrost start
6
th
workdays defrost start
1
st
holiday defrost start
2
nd
holiday defrost start
3
rd
holiday defrost start
4
th
holiday defrost start
5
th
holiday defrost start
6
th
holiday defrost start
1592036000 XW60LH GB r1.0 18.03.2015 XW60LH 5/6