EasyManua.ls Logo

Emerson EC3-D72 - Controller Parameter Configuration; Parameter Selection and Modification; Parameter Groups

Emerson EC3-D72
10 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operating instruction
EC3-D7x Digital Superheat Controller
EC3-D72 with TCP/IP communication capability
Emerson Climate Technologies GmbH www.emersonclimate.eu
Am Borsigturm 31 I 13507 Berlin I Germany Date: 18.07.2017 EC3-D7x_OI_ML_R06_865019.docx
Preparation for Start-up:
Vacuum the entire refrigeration system.
Note: EMERSON Electrical Control Valves EX4-6 are delivered at half open
position. Do not charge system before closure of valve.
Apply supply voltage 24 V to EC3 while the digital input is 0 V (open). The valve
will be driven to close position.
After closure of valve, start to charge the system with refrigerant.
Start the system and check the superheat and operating conditions.
ECD-002 display/keypad unit: (LEDs and button functions)
Procedure for parameter modification using ECD-002:
Note: Some of the functions/parameters (manual control and TCP/IP
configuration) cannot be modified when using ECD-002 comparing to a set-up by
PC via TCP/IP.
Warning:
All alarms are disabled during manual control. We do not recommend
unattended operation of system during manual control.
The parameters can be accessed via the 4-button keypad. The configuration
parameters are protected by a numerical password. The default password is “12”.
To select the parameter configuration:
Press the PRG button for more than 5 seconds, a flashing “0” is displayed
Press or until “12” is displayed (password)
Press SEL to confirm password
Press or to show the code of the parameter that must be changed;
Press SEL to display the selected parameter value;
Press or to increase or decrease the value;
Press SEL to temporarily confirm the new value and display its code;
Repeat the procedure from the beginning "press or to show..."
To exit and save the new settings: Press PRG to confirm the new values and exit
the parameters modification procedure.
To exit without modifying any parameters: Do not press any button for at least
60 seconds (TIME OUT).
Special Functions:
The Special Functions can be activated by:
Press and together for more than 5 seconds, a flashing “0” is displayed.
Press or until the password is displayed (default = “12”).
If password was changed, select the new password.
Press SEL to confirm password
A “0” is displayed and the Special Function mode is activated.
Press or to select the function. The number of special functions is dynamic
and controller dependent. See list below.
0: Reset controller to factory settings (this action is possible only when
digital input is 0 V i.e. open).
1: Displays the current TCP/IP address.
2: Assign temporary 192.168.1.101 as TCP/IP address if EC3-D72x has
different address.
Press SEL to activate the function without leaving the special function mode.
Press PRG to activate the function and leave the special function mode.
Main parameters:
(must be checked and modified if necessary)
Code
Parameter description and choices Min Max
Field
setting
H5
Password
1
199
u0
System refrigerant
0
15
0 = R22 1 = R134a 2 = R507 3 = R404A 4 = R407C
5 = R410A 6 = R124 7 = R744 (subcritical application)
8 = R407A 9 = R407F 10 = R32* 11 = R448A
12 = R449A 13 = R450A 14 = R513A 15 = R1234ze
uP
Installed pressure sensor type
0
2
0 = PT5-07x (for R22 / R134a / R507 / R404A / R407A / R407C /
R407F / R124 / R448A /R449A / R450A / R513A /
R1234ze)
1 = PT5-18x (for R410A/ R32)
2 = PT5-30x (for R410A / R744 / R32)
ut
Installed valve type
1
3
1 = EX4 2 = EX5 3 = EX6
uu
Start valve opening (%)
10
100
u9
Start opening duration (second)
1
30
uL
Low superheat alarm function
0
2
0 = disable (for flooded evaporator)
1 = enable auto reset 2 = enable manual reset
Cut-out at 0.5K (if it maintains 1 min.); Cut-in immediately at 3K
u5
Superheat set-point (K)
If uL enabled (auto or manual)
If uL disabled
3
0.5
30
30
6
u2
MOP function
0
1
0 = disable 1 = enable
u3
MOP set-point (°C) saturation temperature
*
*
**) Factory setting is according to selected refrigerant (u0):
+13°C - R22 +15°C - R134a +7°C - R507
+7°C - R404A +15°C - R407C +15°C - R410A
+50°C - R124 -5°C - R744 +10°C - R407A
+10°C - R407F +10°C - R32 +12°C - R448A
+12°C - R449A +19°C - R450A +13°C - R513A
+24°C - R1234ze
*) Min. and Max. setting values are dependent to selected type of
refrigerant
┌┘
5
Units conversion
0
1
0 = °C, K, bar 1 = °F, R, psig
(Psig values are divided by 10. Example: Display 12.5 is 125 psig)
┌┘
1
Value to show
0
5
0 = Measured superheat (K) 1 = Measured evaporating pressure, (bar);
2 = Valve opening (%) 3 = Measured coil-out temperature (°C)
4 = Calculated evaporating temperature (°C) from the pressure
5 = Compressor capacity in %
u4
Superheat control mode
0
1
0 = Standard, 1 = Slow,
uH
High superheat alarm function
0 = disable, 1 = enable auto reset
1
uA
High superheat alarm setpoint
16
40
ud
High superheat alarm delay, min.
1
15
P2
Freeze protection cut-out, °C
-40
40
P3
Freeze protection cut-in, °C
-37
43
P4
Freeze protection alarm function
0 = disable, 1 = enable auto-reset,
2 = enable manual reset)
0
2
P5
Freeze protection alarm delay, sec.
5
199
P6
Pump-down function
(0 = disable, 1 = enable auto-reset)
0
1
P7
Pump-down cut-out, barg
-0,5
18
P8
Pump-down time delay, sec.
0
199
P9
Low pressure alarm function
(0 = disable, 1 = enable auto-reset,
2 = enable manual reset)
0
2
PA
Low pressure alarm cut-out, barg
-0,8
17,7
Pb
Low pressure alarm delay, sec.
5
199
Pd
Low pressure alarm cut-in, barg
-0,5
18
L2
Output logic
0
3
0: Alarm = normal, pump down. = normal
1: Alarm = inverse, pump down. = normal
2: Alarm = normal, pump down. = inverse
3: Alarm = inverse, pump down. = inverse
Blinking: valve is closing
ON: valve is fully close
Blinking: valve is opening
ON: valve is fully open
ON: demand
OFF: no demand
Blinking: pump
down
ON: alarm
OFF: no alarm
Parameters setting/saving
Selecting/confirming
Next parameter/
value (higher)
Next parameter/
value (lower)
Prg&Sel (5 sec)
Manual reset for
blinking alarm codes

Other manuals for Emerson EC3-D72

Related product manuals