3. Connect one wire of the 3‐conductor shielded cable between terminal 1 on the feedback unit and terminal 1 on the
base unit.
4. Connect the second wire of the 3‐conductor shielded cable between terminal 2 on the feedback unit and terminal 2
on the base unit.
5. Connect the third wire of the 3‐conductor shielded cable between terminal 3 on the feedback unit and terminal 3
on the base unit.
6. Connect the cable shield or drain wire to the ground screw in the feedback connections terminal box of the base
unit.
Note
Do not connect the shield or drain wire to any terminal on the feedback unit, to the earth ground, or any other alternative ground.
7. Replace and hand‐tighten all covers.
8. Proceed to Step 4—Configure the Digital Valve Controller on page 29.