DVC6000f Series
March 2006
1-8
Table 1-4. Hazardous Area Classifications for United States (FM)
CERTIFICATION
BODY
TYPE
CERTIFICATION OBTAINED ENTITY RATING
TEMPERATURE
CODE
ENCLOSURE
RATING
FM
DVC60x0F
DVC60x0FS
(x = 1,2,3)
(Intrinsic Safety)
Class/Division
Class I,II,III Division 1 GP
A,B,C,D,E,F,G per drawing
GE04332 (including FISCO)
FIELDBUS
T5(T
amb
v 80C)
4X
V
max
= 24 Vdc
I
max
= 226 mA
C
i
= 5 nF
L
i
= 0 mH
P
i
= 1.4 W
FISCO
V
max
= 17.5 Vdc
I
max
= 380 mA
C
i
= 5 nF
L
i
= 0 mH
P
i
= 5.32 W
(Explosion Proof)
Class/Division
Class I, Division 1 GP B,C,D
− − −
T6(T
amb
v 80C)
4X
Class I Division 2 GP A,B,C,D
Class II,III Division 1 GP E,F,G
Class II,III Division 2 GP F,G
− − −
T6(T
amb
v 80C)
4X
DVC6005F
(Intrinsic Safety)
Class/Division
Class I,II,III Division 1 GP
A,B,C,D,E,F,G per drawing
GE07475 (including FISCO)
FIELDBUS
T6(T
amb
v 60C)
4X
V
max
= 24 Vdc
I
max
= 226 mA
C
i
= 5 nF
L
i
= 0 mH
P
i
= 1.4 W
V
oc
= 8.6 Vdc
I
sc
= 2.3 mA
C
a
= 6.2 µF
L
a
= 100 mH
P
o
= 5 mH
FISCO
V
max
= 17.5 Vdc
I
max
= 380 mA
C
i
= 5 nF
L
i
= 0 mH
P
i
= 5.32 W
V
oc
= 8.6 Vdc
I
sc
= 2.3 mA
C
a
= 6.2 µF
L
a
= 100 mH
P
o
= 5 mW
(Explosion Proof)
Class/Division
Class I Division 1 GP C,D
− − −
T6(T
amb
v 60C)
4X
Class I Division 2 GP A,B,C,D
Class II,III Division 1 GP E,F,G
Class II,III Division 2 GP F,G
− − −
T6(T
amb
v 60C)
4X
DVC60x5
(x = 1,2,3)
(Intrinsic Safety)
Class/Division
Class I,II,III Division 1 GP A,B,C,
D,E,F,G per drawing GE07475
V
max
= 10 Vdc
I
max
= 4 mA
C
i
= 0 nF
L
i
= 0 mH
P
i
= 10 mW
T4(Tamb v 125C)
T5(Tamb v 95C)
T6(Tamb v 80C)
4X
(Explosion Proof)
Class/Division
Class I Division 1 GP A,B,C,D
− − −
T4(Tamb v 125C)
T5(Tamb v 95C)
T6(Tamb v 80C)
4X
Class I Division 2 GP A,B,C,D
Class II,III Division 1 GP E,F,G
Class II,III Division 2 GP F,G
− − −
T4(Tamb v 125C)
T5(Tamb v 95C)
T6(Tamb v 80C)
4X