Quick Start Guide
D103556X012
DVC6200 Digital Valve Controllers
August 2015
60
1 SEE NOTES IN FIGURE 54
GE60771 Sheet 11, Rev. B
ZONE 0, Ex ia IIC
ZONE 20, Ex ia IIIC
LOOP TERMINALS
Ui = 30 VDC
Ii = 130 mA
Ci = 15 nF
Li = 0.55 mH
Pi = 1.0 W
HAZARDOUS LOCATION
POWER MAY BE APPLIED TO
EITHER THE LOOP TERMINALS
OR OUTPUT TERMINALS OR TO
BOTH SETS OF TERMINALS AT
THE SAME TIME
UNITS WITHOUT THE I/O
PACKAGE WILL NOT HAVE
“OUTPUT TERMINALS”
AVAILABLE FOR CONNECTION
1 NOTE 5
Figure 50. ATEX Loop Schematics—FIELDVUE DVC6200 HW2 and DVC6200 SIS
T5 ≤ 80_C T5 ≤ 80_C
NON‐HAZARDOUS LOCATION
ATEX APPROVED BARRIER
HW2 - WITH OR WITHOUT I/O PACKAGE
DVC6200, DVC6200S
NOTE 1, 3, 4 1
ATEX APPROVED BARRIER
NOTE 1, 3, 4 1
OUTPUT TERMINALS
Ui = 28 VDC
Ii = 100 mA
Ci = 15 nF
Li = 0.5 mH
Pi = 1.0 W
WITH
I/O PACKAGE
WITHOUT
I/O PACKAGE
ZONE 0, Ex ia IIC ZONE 20, Ex ia IIIC
WITH
I/O PACKAGE
WITHOUT
I/O PACKAGE
T CODE T AMB T CODE T AMB
T6 ≤ 74_C T6 ≤ 61_C T85_C ≤ 74_C T85_C ≤ 61_C
T91_C ≤ 80_C T104_C ≤ 80_C
MAX
SURFACE
TEMP
MAX
SURFACE
TEMP
T AMB
T AMB