Instruction Manual Supplement
D103988X012
DVC6200 SIS
October 2017
3
b. Set the HighLimit/Cutoff Point to 0.5-1% less than the Travel High High Alert Point in the Travel Alerts tab (refer
to figure 2 for Travel Alerts tab).
Figure 2. Travel Alerts Tab
8. Once the Cutoff Points are set, download to the DVC6200 SIS.
9. When the DVC6200 SIS is placed in service it will throttle between whatever cutoffs are set in step 7.
In the example shown in figure 3, it will be able to throttle between 5 and 95% valve travel.
Figure 3. Detailed Setup > Travel/Pressure Control