Quick Start Guide
D103556X012
DVC6200 Digital Valve Controllers
August 2015
61
Figure 51. ATEX Loop Schematics—FIELDVUE DVC6205, DVC6205 SIS, and DVC6215
1 SEE NOTES IN FIGURE 54
GE60771 Sheet 12, Rev. B
ZONE 0, Ex ia IIC
ZONE 20, Ex ia IIIC
REMOTE
FIELD WIRING
TERMINAL BOX
HAZARDOUS LOCATION
POWER MAY BE APPLIED TO EITHER
THE LOOP TERMINALS OR OUTPUT
TERMINALS OR TO BOTH SETS OF
TERMINALS AT THE SAME TIME
UNITS WITHOUT THE I/O PACKAGE
WILL NOT HAVE “OUTPUT
TERMINALS” AVAILABLE FOR
CONNECTION
NOTE 5
T5 ≤ 80_C
1
NON‐HAZARDOUS LOCATION
ATEX APPROVED BARRIER
HW2 - WITH OR WITHOUT I/O PACKAGE
DVC6205
NOTE 1, 3, 4 1
T4 ≤ 125_C
ATEX APPROVED BARRIER
NOTE 1, 3, 4 1
DVC6215
Ui = 30 VDC
Ii = 226 mA
Ci = 50 nF
Li = 0.55 mH
Pi = 1.4 W
Vo = 30 VDC
Io = 21.2 mA
Ca = 55 nF
La = 78 mH
Po = 160 mW
LOOP TERMINALS
OUTPUT TERMINALS
FIELD WIRING
TERMINAL BOX
T6 ≤ 74_C
NOTE 1, 3 1
ZONE 0, Ex ia IIC
ZONE 0, Ex ia IIC
DVC6215
T CODE T AMB
T5 ≤ 95_C
WITH
I/O PACKAGE
WITHOUT
I/O PACKAGE
ZONE 0, Ex ia IIC ZONE 20, Ex ia IIIC
WITH
I/O PACKAGE
WITHOUT
I/O PACKAGE
T6 ≤ 80_C
T CODE T AMB T CODE T AMB
T85_C ≤ 74_C T85_C ≤ 61_C
T91_C ≤ 80_C T104_C ≤ 80_C
MAX
SURFACE
TEMP
MAX
SURFACE
TEMP
T AMB
T AMB
T5 ≤ 80_C
T6 ≤ 61_C
DVC6205
TYPE
Ui = 30 VDC
Ii = 130 mA
Ci = 15 nF
Li = 0.55 mH
Pi = 1.0 W
Ui = 28 VDC
Ii = 100 mA
Ci = 15 nF
Li = 0.5 mH
Pi = 1.0 W