EasyManua.ls Logo

Emerson Fisher FIELDVUE DVC6215 - Page 69

Emerson Fisher FIELDVUE DVC6215
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Quick Start Guide
D103556X012
DVC6200 Digital Valve Controllers
August 2015
69
1 SEE NOTES IN FIGURE 60
IECEx
APPROVED
ENTITY DEVICE
HAZARDOUS LOCATION
NON‐HAZARDOUS LOCATION
ZONE 0, Ex ia IIC
Ui = 24 VDC
Ii = 380 mA
Ci = 5 nF
Li = 0 mH
Pi = 1.4 W
IECEx APPROVED
BARRIER
NON‐HAZARDOUS LOCATION
HAZARDOUS LOCATION
ENTITY FIELDBUS LOOP
IECEx APPROVED
FISCO BARRIER
IECEx APPROVED
FISCO TERMINATOR
IECEx
APPROVED
FISCO DEVICE
DVC6200F, DVC6200FS
DVC6200P, DVC6200PS
FISCO LOOP
1 NOTE 1, 3, 4
NOTE 1, 3 1
1 NOTE 5
1 NOTE 2, 3, 4
NOTE 2, 3 1
GE42990 Sheet 4, Rev. E
ZONE 0, Ex ia IIC
T CODE T (amb)
T4 80_C
T5 77_C
T6 62_C
Figure 58. IECEx Loop Schematics—FIELDVUE DVC6200f and DVC6200p
T CODE T (amb)
T4 80_C
T5 77_C
T6 62_C
GE42990 Sheet 3, Rev. E
DVC6200F, DVC6200FS
DVC6200P, DVC6200PS
Ui = 17.5 VDC
Ii = 380 mA
Ci = 5 nF
Li = 0 mH
Pi = 5.32 W