Type 99
8
Clean out all pipelines before installation and check 
to be sure the regulator has not been damaged or 
collected foreign material during shipping.
Apply pipe compound to the external pipe threads 
only with a threaded body or use suitable line gaskets 
and good bolting practices with a anged body. This 
regulator may be installed in any position desired as 
long as the ow through the body is in the direction 
indicated by the arrow on the body. Install a three-valve 
bypass around the regulator if continuous operation is 
necessary during maintenance or inspection.
Although the standard orientation of the actuator and 
pilot to the main valve body is as shown in Figure 1, this 
orientation may be changed as far as the inlet tubing 
(key 24, Figure 9 or 17) will permit by loosening the 
union nut (key 14, Figure 9), rotating the actuator lower 
casing (key 29, Figure 9) as desired and tightening 
the union nut. To keep the pilot spring case from being 
plugged or the spring case from collecting moisture, 
corrosive chemicals or other foreign material, the vent 
must be pointed down, oriented to the lowest possible 
point on the spring case or otherwise protected. Vent 
orientation may be changed by rotating the spring case 
with respect to the pilot body.
To remotely vent a low-pressure pilot, install the vent 
line in place of the pressed-in vent assembly (key 60, 
Figure 9). Install obstruction-free tubing or piping into 
the 1/4 in. / 6.4 mm vent tapping. Provide protection 
on a remote vent by installing a screened vent cap into 
the remote end of the vent pipe.
To remotely vent a high-pressure pilot, remove the 
threaded-in vent assembly (key 72, Figure 12) 
from the high-pressure pilot spring case and install 
obstruction-free tubing or piping into the 1/4 in. /  
6.4 mm vent tapping. Provide protection on a remote 
vent by installing a screened vent cap into the remote 
end of the vent pipe. 
An upstream pilot supply line is not required 
because of the integral pilot supply tubing (key 24, 
Figure 9 or 17). However, as long as the 1/4 NPT 
tapping in the main valve body is plugged, this 
tubing may be disconnected from both the main 
valve and lter assembly (key 75, Figures 9 and 16) 
in order to install a pilot supply line from a desired 
remote location into the lter.
If the maximum pilot inlet pressure will be exceeded 
by main valve pressure, install a separate pressure 
reducing regulator (if not already provided) in the pilot 
supply line. 
A Type 99 regulator has two 1/2 NPT control line 
pressure taps on opposite sides of the lower casing 
(key 29, Figure 9). The regulator normally comes from 
the factory with the tap closest to the regulator outlet left 
unplugged for the downstream control line as shown in 
Figure 1 and with opposite tap plugged.
Attach the control line from the unplugged tap 2 to 
3 ft / 0.61 to 0.91 meter downstream of the regulator 
in a straight run of pipe. If impossible to comply with 
this recommendation due to the pipe arrangement, it 
may be better to make the control line tap nearer the 
regulator outlet rather than downstream of a block 
valve. Do not install the tap near any elbow, swage or 
nipple which might cause turbulence.
In many instances, it will be necessary to enlarge the 
downstream piping to keep ow velocities within good 
engineering practices. Expand the piping as close to 
the regulator outlet as possible.
!
WARNING
Adjustment of the pilot control spring to 
produce an outlet pressure higher than 
the upper limit of the outlet pressure 
range for that particular spring can cause 
personal injury or equipment damage 
due to bursting of pressure-containing 
parts. Dangerous accumulation of gases 
may also cause bursting if the maximum 
actuator emergency casing pressure in 
the Specications section is exceeded. If 
the desired outlet pressure is not within 
the range of the pilot control spring, 
install a spring of the proper range 
according to the Maintenance section.
Each regulator is factory-set for the pressure setting 
specied on the order. If no setting was specied, outlet 
pressure was factory-set at the midrange of the pilot 
control spring. In all cases, check the control spring 
setting to make sure it is correct for the application.
Overpressure Protection
The Type 99 regulator has an outlet pressure 
rating lower than its inlet pressure rating. Complete 
downstream overpressure protection is required if 
the actual inlet pressure can exceed the regulator 
outlet pressure rating or the pressure ratings of any 
downstream equipment. Although the Type H110 
relief valve provides sufcient relief capacity to protect