Type 99
9
the extra high-pressure pilot of 1000 psig / 69.0 bar 
maximum inlet pressure in case the Type 1301F supply 
regulator fails open, this protection is insufcient if the 
main valve body fails open. Regulator operation within 
ratings does not preclude the possibility of damage from 
external sources or from debris in the lines. A regulator 
should be inspected for damage periodically and after 
any overpressure condition.
!
WARNING
The 1000 psig / 69.0 bar maximum 
inlet regulator must not be used on 
hazardous gas service unless the 
Type H110 relief valve can be vented 
into a safe area. If vented gas can 
accumulate and become a hazard in 
enclosed conditions such as in a pit, 
underground or indoors, the relief valve 
must be repiped to carry the gas to a 
safe location.
A repiped vent line or stack must be 
located to avoid venting gas near 
buildings, air intakes or any hazardous 
location. The line or stack opening must 
be protected against condensation, 
freezing and clogging. 
Startup
Key numbers are referenced in Figures 9 through 15 
for a low or high-pressure pilot and in Figure 18 for an 
extra high-pressure pilot. 
1.  Very slowly open the upstream block valve.
2.  Slowly open the hand valve (if used) in the control 
line. The unit will control downstream pressure 
at the pilot control spring setting. If changes in 
the pressure setting are necessary, follow the 
procedure in the Adjustment section. 
3.  Slowly open the downstream block valve.
4.  Slowly close the bypass valve, if any.
5.  Check all connections for leaks.
Adjustment
With proper installation completed, perform the 
adjustment procedure while using pressure gauges to 
monitor pressure.
The only adjustment on the regulator is the reduced 
pressure setting affected by the pilot control spring 
(key 43, Figure 9, 12, 14 or 18). Remove the closing 
cap assembly (key 46, Figure 9, 14 or 15) and turn 
the adjusting screw (key 45, Figure 9, 14, 15 or 18). 
Turning the adjusting screw clockwise into the spring 
case increases the controlled or reduced pressure 
setting. Turning the adjusting screw counterclockwise 
decreases the reduced pressure setting. Always 
replace the closing cap after making adjustments.
Shutdown
Installation arrangements may vary, but in any 
installation, it is important to open and close valves 
slowly and the outlet pressure be vented before 
venting inlet pressure to prevent damage caused by 
reverse pressurization of the regulator.
1.  Isolate the regulator from the system. Close the 
upstream block valve to the pilot and regulator inlet.
2.  Close the downstream block valve to the pilot 
sense connection and the regulator outlet.
3.  Vent the downstream pressure by slowly opening 
the vent valve to vent all pressures.
4.  Vent inlet pressure slowly through the vent valve to 
release any remaining pressure in the regulator.
Maintenance
Regulator parts are subject to normal wear and must be 
inspected and replaced as necessary. The frequency 
of inspection and replacement of parts depend on the 
severity of service conditions or the requirements of 
local, state and federal rules and regulations.
!
WARNING
Avoid personal injury or damage to 
property from sudden release of pressure 
or uncontrolled gas or other process uid. 
Before starting to disassemble, isolate 
the pilot or regulator from all pressure 
and cautiously release trapped pressure 
from the pilot or regulator. Use gauges to 
monitor inlet, loading and outlet pressures 
while releasing these pressures.