FloBoss™ S600+ Flow Computer Modbus Specification Manual   
D301904X012 
June 2024  
4 
•
 
Gateway = 192.168.102.1 
 
Network Port 2 
•
 
IP Address = 192.168.102.130  
•
 
Subnet = 255.255.255.128 
 
In the second example below, messages to an address outside of the 192.168.102.x range 
would be sent to gateway 192.168.102.129 via network port 2 (the gateway is on network 
port 2 subnet). 
Network Port 1  
•
 
IP Address = 192.168.102.2  
•
 
Subnet = 255.255.255.128 
•
 
Gateway = 192.168.102.129 
 
Network Port 2 
•
 
IP Address = 192.168.102.130  
•
 
Subnet = 255.255.255.128 
3.4  Network Configuration (06.30a onwards) 
From binary.app 06.30a onwards, both network ports had a full TCP/IP stack 
implementation. This allows separate gateways to be configured for each network port if 
required. 
Section 4.  Modbus  
Modbus is the standard interface to the FloBoss
 
S600+ The protocol is based on 
Gould/Modicon Modbus. The FloBoss
 
S600+ supports both Modbus slave and Modbus 
master interfaces.   
The following Config600 tools (Config Transfer, Remote Archive Uploader and the Logicalc 
Editor connection) interface to the FloBoss
 
S600+ using Modbus. This link uses the special 
“function code 65,” with specially defined FloBoss
 
S600+ sub-functions to provide file 
transfer, system edit commands, and other specialized functionality.  
4.1  Configuration  
The system firmware supports up to 20 communications links. Links can have individual 
Modbus maps or can share common Modbus maps depending on the configuration 
requirements.