34 Chapter 10 Maintenance
Note
10,000VA model is shown in Figure 10-2; 5000VA / 6000VA model arrangement is the same except smaller.
5. Grasp the battery handle and pull one of the internal battery packs out of the UPS, as shown in Figure 10-3.
Repeat this step if both battery packs will be replaced. Each model has two battery packs.
Internal
battery pack
Battery handle
Pull out with
battery handle
5000VA & 6000VA models
Internal
battery pack
Battery
handle
Pull out with
battery handle
10,000VA models
Figure 10-3 Pulling out the battery packs
6. Unpack a new internal battery pack. Take care not to destroy the packing.
Compare the new and old internal battery packs to make sure they are the same type and model.
If they are the same, proceed with Step 7; if they are different, stop and contact your local Emerson representative or
Emerson Channel Support.
7. Line up and slide in the new internal battery pack.
8. Repeat Steps 6 and 7 if replacing both battery packs. Each model has two battery packs
9. Reconnect the battery plugs and battery receptacles.
10. Gently push the battery wire into the UPS battery compartment.
11. Reattach the front battery door with the six screws.
12. Reattach the front plastic bezel cover to the UPS.
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual