Programming
CM-2201/CM-2202
7.3.11
Reset Module
This selection resets controller memory parameters to
factory default values. If the controllers memory becomes
corrupt, resetting the module will force the controller to
overwrite each register and may correct any problems that
exist.
1.
Display Mode: Advance
2.
Range: yes, no
3.
Default: no
7.4
Program- System Test
7.4.1
System Test
This message displays the name of the sub-menu when
entered.
1.
Display Mode: Advanced
2.
Range: N/A
3.
Default: N/A
7.4.2
Alarm Output Test
This function is used for testing and commissioning
purposes allowing the alarm output to be forced On either
for
a short period of time or continuously. At the end of the
specified time duration, the testing option is automatically
disabled. The alarm test function will not operate if the
alarm configuration is set to disable and the message
“ALARM DISABLED” will appear.
1.
Display Mode: Advanced
2.
Range: 1-24 hours, Disabled, Continuously
3.
Default: disabled
7.4.3
Heater Test
This function overrides heater control for maintenance
purposes. For normal operation, set to “disable”. If a period
of time is selected, the heater is forced On or Off for the
selected interval. If “continuous” is selected the heater is
forced On or Off until “disable" is selected.
1.
Display Mode: Advanced
2.
Range: 1-24 hours, Disabled, On Continuously
3.
Default: disabled
Ground Fault Test
This function will test the ground fault trip function of the
controller t
o ensure proper operation. When selected, the
controller will generate an artificial ground fault current;
if
the ground fault current is sensed as being greater than 30
mA, the test passes. The GF test function will verify actual
ground fault current and heater trip. Status of the test will
be displayed
as pass or fail.
If this test has been
invoked
by the “Now” option and it
passes, the user is prompted to reset the ground fault
trip, at which time the load is capa- ble of being re-
energized as required. If this test has been invoked by
the “Autotest” option and it passes, the load is allowed
to be reenergized as required. If this test has been
invoked by the Autotest cycle and it fails, an Autotest
alarm is generated but the load is allowed to be
reenergized
as required.
4.
Display Mode: Advanced
5.
Range:Autotestcycle,Now,Disabled
6.
Default: Disabled
17
©2017 Nelson Heat Tracing Systems
www.nelsonheaters.com
GA2497 Rev.5