EasyManua.ls Logo

Emerson PACMotion VFD Series - Page 6

Emerson PACMotion VFD Series
10 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PACMotion VFD Input/Output Chokes Installation Guide Section 2
GFK-3185A August 2020
Input Line Chokes 3
Part Number
VFD
Size
Connection
(mm
2
)
L
(mm)
H
(mm)
B
(mm)
N1
(mm)
N2
(mm)
ØD
(mm)
Rated
Volts
Rated
Amps
Inductance
(mH)
Weight
(kg)
IC866-ICH-006-
603-20
1
2.5
95
107
56
56
43
4.8 x 9
500
Max
6
4.8
1.3
IC866-ICH-010-
603-20
2
2.5
125
127
71
100
55
5 x 8
10
2.9
2.5
IC866-ICH-036-
603-20
3
10
190
205
82
170
58
8 x 12
36
0.81
7.2
IC866-ICH-050-
603-20
4
16
190
220
102
170
78
8 x 12
50
0.58
8.7
IC866-ICH-090-
603-20
5
35
240
280
107
185
85
10 x
18
90
0.32
16
Figure 3: IC866-ICH-006-603-20, IC866-ICH-010-603-20
Figure 4: IC866-ICH-036-603-20, IC866-ICH-050-603-20,
IC866-ICH-090-603-20
Part Number
VFD
Size
Connection
D2 (mm)
L
(mm)
H
(mm)
B
(mm)
N1
(mm)
N2
(mm)
ØD
(mm)
Rated
Volts
Rated
Amps
Inductance
(μH)
Weight
(kg)
IC866-ICH-
200-603-00
6
9
310
260
180
224
117
10 x 18
500
200
73.5
35
IC866-ICH-
300-603-00
7
9
370
310
180
248
139
10 x 18
300
49.0
48
Figure 5: IC866-ICH-200-603-00
Figure 6: IC866-ICH-300-603-00