Battery & Energy Pack Manual Chapter 3
GFK-2741J Oct 2019
Energy Packs 24
Figure 8: Drilling Pattern for Direct Panel Mounting
3.2.5 Cable Connections
Figure 9: Input Power and Output Power/Control Connections
Connecting Input Power to the Energy Pack
You will need:
A power cord with 18 AWG (0.82mm2) copper wires
An 18 AWG (0.82mm2) copper wire for frame ground
An input power terminal block provided (Weidmüller part number 1748010000)
A small flat¬ head screwdriver (such as a 1.4 mm jeweler’s screwdriver)
A 24Vdc, 72 W minimum power supply, that must provide reliable grounding and
Secondary Extra Low Voltage (SELV) output or other form of isolating secondary
circuit.