PACSystems™ RX3i and RSTi-EP CPU Reference Manual Section 5
GFK-2222AK October 2019
Communications 132
5.2.7 Communications Coprocessor Module (CMM)
PACSystems does not support the following with an IC697CMM711:
Access to Symbolic variables
WAIT mode COMMREQs.
Connecting the programming software to the CPU through the CMM’s serial ports.
Permanent datagrams.
The following restrictions apply when using the IC697CMM711 with PACSystems:
Access to %W references is partially supported. Only offsets 065535 of %W can be
accessed via the CMM.
The Program Name is currently always LDPROG1 for PACSystems.
Reads and writes beyond currently configured reference table limits will report a
minor code error of 90 (REF_OUT_OF_RANGE) instead of F4 (INVALID_PARAMETER)
as reported on the Series 90-70.
In case of ERROR NACK, the Control Program number, privilege level and other
piggyback status data will be set to 0.
PACSystems CPUs return the major/minor type of the 90-70 CPX935 (major type 12,
minor type 35) to the CMM scratch pad memory when communicating with a CMM.
Control Program Number will be returned as 01 in PACSystems instead of FF as
reported on the Series 90-70.
Note: For details on operation of the IC697CMM711, refer to the Series 90 PLC Serial
Communications User’s Manual, GFK-0582.
5.2.8 Programmable Coprocessor Module (PCM)
PACSystems does not support the following with an IC697PCM711:
Connecting the programming software to the CPU through the serial ports on the
PCM711.
Access to Symbolibc variables.
WAIT mode COMMREQs.
The following C functions are not supported:
chk_genius_bus
chk_genius_device
get_cpu_type_rev
get_memtype_sizes