PACSystems™ RX3i and RSTi-EP CPU Reference Manual Section 3
GFK-2222AK October 2019
CPU Configuration 48
Settings Parameters
Power-up Mode
Selects the CPU mode to be in effect immediately after power-up.
Choices: Last, Stop, Run.
Default: Last (the mode it was in when it last powered down).
Note: If the battery or Energy Pack is missing or has failed and if Logic/Configuration
Power-up Source is set to Always RAM, the CPU powers up in STOP Mode
regardless of the setting of the Power-up Mode parameter.
Modbus
Address Space
Mapping Type
Specifies the type of memory mapping to be used for data transfer between Modbus
TCP/IP clients and the PACSystems controller.
Choices:
Disabled: The Disabled setting is intended for use in systems containing Ethernet
firmware that does not support Modbus TCP.
Standard Modbus Addressing: Causes the Ethernet firmware to use the standard map,
which is displayed on the Modbus TCP Address Map tab.
Default: Disabled
For details on the PACSystems implementation of Modbus/TCP server, refer to
PACSystems & RX3i TCP/IP Ethernet Communications User Manual, GFK-2224.
Universal Serial
Bus
RX3i CPE302/CPE305/CPE310/CPE330 CPUs only. Enables or disables the USB port for use
with RDSD (Removable Data Storage Devices). The USB port is enabled by default in the
CPE302/CPE305/CPE310/CPE330 and in the hardware configuration.
If a CPU310 configuration is stored to a CPE310, the USB port will be enabled.
LAN1 Mode
RX3i CPE330/CPE400/CPL410 and RSTi-EP CPE100/CPE115 CPUs only.
CPU LAN1 port mode.
Choices:
Ethernet: LAN port 1 is used for Ethernet communications.
Default: Ethernet.