EasyManua.ls Logo

Emerson ROC364 - Switch to Discrete Inputs; Switch to Pulse Inputs

Emerson ROC364
146 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ROC364 Instruction Manual
C-5 I/O Simulation Rev Jun/05
C.6 Switch to Discrete Inputs
Figure C-12 shows how to use a switch and power source to simulate a device transmitting a discrete
voltage level to a Discrete Input Isolated module.
AUX PWR OUT 1
+
SWITCH
B
C
A
N/C
+
R1=10
DOC0187A
DI ISO
3.3K
Figure C-12. Switch Input to DI Isolated Module
Figure C-13 shows how to use a switch to simulate relay contacts to a Discrete Input Source module.
SWITCH
R1=10
C
-
B
A
+
N/C
3.3K
DOC0188A
DI SRC
Vs
Figure C-13. Switch Input to DI Source Module
C.7 Switch to Pulse Inputs
Figure C-14 shows how to use a switch to simulate relay contacts to a Pulse Input Source module.
AUX PWR OUT 1
-
SWITCH
+
C
B
-
+
A
N/C
R1=10
DOC0190A
PI ISO
2.2K
Figure C-14. Switch to PI Source Module