EasyManua.ls Logo

Emerson ROC364 - Page 52

Emerson ROC364
146 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ROC364 Instruction Manual
3-18 Input and Output Modules Rev Jun/05
NOTE: The RTD module input can be calibrated before installing it in the field when short wire
runs will be used, but if the RTD module is used as a temperature input to a flow calculation,
then the RTD should be calibrated at the same time as the pressure inputs.
A4464821
1
ABC
DECADE BOX
RTD
WHTC
WHT
RED
B
A
Figure 3-21. Calibration Setup
Table 3-1. Calibration Resistance Values
ALPHA –50ºC (58ºF) 100ºC (212ºF)
0.00385 80.31 Ohms 138.50 Ohms
0.00392 79.96 Ohms 139.16 Ohms
NOTE: Resistance values for RTD probes with other alpha
values can be found in the temperature-to-resistance
conversion table for that probe.
1. Connect the decade box as shown in Figure 3-21.
2. Set the decade box to the –50°C (–58°F) resistance value corresponding to the RTD alpha value
in Table 3-1.
3. Enter the value displayed for “Raw A/D Input” as the value for “Adjusted A/D 0%” using the
Analog Inputs configuration screen for the RTD input. Refer to ROCLINK > Configure > I/O >
AI Points Advanced tab.
4. Set the decade box to the 100°C (212°F) resistance value given in Table 3-1.
5. Enter the value displayed for “Raw A/D Input” as the value for “Adjusted A/D 100%” using the
Analog Inputs Advanced configuration screen for the RTD input.
6. Enter –50°C (–58°F) for “Low Reading EU” using the Analog Inputs configuration screen. Refer
to ROCLINK > Configure > I/O > AI Points General tab.
7. Enter 100°C (212°F) for the “High Reading EU” using the Analog Inputs configuration screen.
8. Click Apply to save the changes.

Table of Contents

Related product manuals