5
Manual Supplement
00809-0400-2410, Rev AA
Rosemount 2410 Tank Hub
March 2016
Rosemount 2410 Tank Hub
1.2 Electrical installation
1.2.1 Rosemount 2410 Tank Hub connections
Figure 1-4. Terminal Block in the Explosion-Proof/Flameproof Compartment
Table 1-2. Terminal Assignment for Non-Intrinsically Safe Side
Terminal Designation Function
1 N / - Power, Neutral / DC -
2 L / + Power, Line / DC +
3 K1 A Relay 1 output (optional). Hardware configurable NO/NC.
4 K1 com Relay 1 common
5 K2 A Relay 2 output (optional). Hardware configurable NO/NC.
6 K2 com Relay 2 common
7a/7b P Bus B Primary communication bus B
8a/8b P Bus A Primary communication bus A
9 S Pwr - Secondary bus power - (optional)
10 S Pwr + Secondary bus power +(optional)
11 S Bus B Secondary communication bus - (optional)
12 S Bus A Secondary communication bus + (optional)
PE PE Power supply protective ground
GND_1 GND_1 Housing chassis/shield Primary bus
GND_2 GND_2 Housing chassis/shield Secondary bus
Secondary field bus
Primary field bus