Manual Supplement
00809-0400-2410, Rev AA
March 2016
Rosemount
™
2410 Tank Hub
Enraf
®
emulation instruction
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 1
Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5
Configuration using the FBM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7
Configuration using the EBM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 14
Advanced information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 23
1.1 Introduction
The purpose of this document is to provide guidelines on how to change from Enraf to
Rosemount equipment by exchanging gauges. When an Enraf gauge is replaced with a
Rosemount gauge, it is necessary to configure the Rosemount 2410 Tank Hub for emulation.
The Rosemount field devices, for example Rosemount 5900 Radar Level Gauge and Rosemount
2240S Temperature Transmitter, are connected to the tank hub using the intrinsically safe
Tankbus as usual. Emulation is done in the tank hub only. Each tank hub can emulate up to 10
tanks (10 separate Enraf gauges).
Figure 1-1. Rosemount Devices Replacing Old Gauges in an Existing Enraf System
Entis
PLC
CIU
Rosemount
5900S Radar
Level Gauge
Rosemount 2410
Tank Hub
Rosemount 3051S
Pressure Transmitter
Rosemount 2240S
Temperature Transmitter
with sensor