8
Manual Supplement
00809-0400-2410, Rev AA
Rosemount 2410 Tank Hub
March 2016
Rosemount 2410 Tank Hub
5. Set the communication parameters:
6. Select the Enable Channel check box to activate the protocol channel.
7. Select OK to store the current configuration and close the configuration window.
1.3.2 Install Rosemount 2410 Tank Hub in WinSetup
The TankMaster WinSetup wizard is the recommended tool for installing the tank hub.
The installation wizard covers basic configuration of the tank hub.
Perform the following steps to start the installation wizard in TankMaster WinSetup:
1. In the Workspace window select the Device folder.
2. Right click and select Install New, or from the Service menu select the
Devices/Install New option. The Select Device window appears.
Port The COM port the FBM will connect to
Baud rate 4800
Stop bits 1
Parity None
Modem FBM 2180
Handshaking None
Reply timeout 1000 ms
Retries 3
Description Text describing the configured channel