2 Configuration
2.1 Bench calibration
There are three ways to configure the transmitter:
• Field Communicator
• Rosemount 248 PC Programming Kit
• Custom at the factory using the C1 option code
Refer to the Rosemount 248 Reference Manual and the Field Communicator
User Guide for more information.
Connecting a field communicator
The Field Communicator Field Device Revision Dev v1, DD v1or later is
required for complete functionality.
Figure 2-1: Connecting a Field Communicator to a Bench Loop
A. Rosemount 248 Transmitter
B. 250 Ω ≤ RL ≤ Ω 1100
C. Field Communicator
D. Power supply
E. Recorder (optional)
F. Ammeter (optional)
Note
Do not operate when power is below 12 Vdc at the transmitter terminal.
February 2021 Quick Start Guide
Quick Start Guide 5