3. In the Device Connection View, double-click the modem icon.
4. Double-click the device icon.
6.2.2 Connect to device using a handheld communicator
Procedure
Turn on the handheld communicator and connect to the device.
6.2.3 Configure device
HART
®
Device Revision 3
Procedure
1. Select Configure/Setup > Basic Setup.
2. Configure steps 1- 6 in the Basic Setup (Variable Mapping, Probe,
Geometry, Environment, Volume, and Analog Out).
3. Select Finish.
4. Select Device Specific Setup.
5. Select Restart Device.
HART
®
Device Revision 4
Procedure
1. Select Configure > Guided Setup.
2. Select Level Measurement Setup and follow the instructions.
3. Select Device Specific Setup.
4. Run Verify Level to check your level measurement.
5. Consider optional setup, such as Volume and Display.
FOUNDATION
Fieldbus
Procedure
1. Select Configure > Guided Setup.
2. Select Level Measurement Setup and follow the instructions.
3. (Optional) Select Volume Calculation Setup.
4. Select Device Specific Setup.
5. Select Restart Measurement.
February 2019 Quick Start Guide
Quick Start Guide 23