2. WARNING – The apparatus enclosure contains aluminum and is
considered to constitute a potential risk of ignition by impact or
friction. Care must be taken into account during installation and use to
prevent impact or friction.
9.5.2 I5 Intrinsic Safety (IS), Nonincendive (NI)
Certificate
FM16US0444X
Standards
FM Class 3600 – 2011; FM Class 3610 – 2010; FM Class 3611 –
2004; FM Class 3615 – 2006; FM Class 3810 – 2005; ANSI/ISA
60079-0 – 2013; ANSI/ISA 60079-11 – 2012; ANSI/NEMA 250 –
2003;
Markings
IS CL I, II, III, DIV 1, GP A, B, C, D, E, F, G in accordance with
control drawing 9240030-936; IS (Entity) CL I, Zone 0, AEx ia IIC
T4 in accordance with control drawing 9240030-936, NI CL I, II,
III DIV 2, GP A, B, C, D, F, G; T4; -50 °C ≤ Ta ≤ 60 °C / 70 °C; Type
4X
Special Conditions for Safe Use (X):
1. WARNING –Potential Electrostatic Charging Hazard – The enclosure
contains non-metallic material. To prevent the risk for electrostatic
sparking the plastic surface should only be cleaned with a damp cloth.
2. WARNING – The apparatus enclosure contains aluminum and is
considered to constitute a potential risk of ignition by impact or
friction. Care must be taken into account during installation and use to
prevent impact or friction.
Ui Ii Pi Ci Li
Entity parameters
HART
30 V 130 mA 1 W 7.26 nF 0
Entity parameters
Fieldbus
30 V 300 mA 1.3 W 0 0
9.5.3 IE FISCO
Certificate
FM16US0444X
Standards
FM Class 3600 – 2011; FM Class 3610 – 2010; FM Class 3611 –
2004; FM Class 3615 – 2006; FM Class 3810 – 2005; ANSI/ISA
60079-0 – 2013; ANSI/ISA 60079-11 – 2012; ANSI/NEMA 250 –
2003;
Markings
IS CL I, II, III, DIV 1, GP A, B, C, D, E, F, G; T4; in accordance with
control drawing 9240030-936; IS CL I, Zone 0 AEx ia IIC T4 in