Ui Ii Pi Ci Li
Entity parameters
HART
30 V 130 mA 1 W 7.26 nF 0
Entity parameters
Fieldbus
30 V 300 mA 1.3 W 0 0
9.6.3 IF FISCO
Certificate
1514653
Standards
CSA C22.2 No.0-M91, CSA C22.2 No.25-1966, CSA C22.2
No.30-M1986, CSA C22.2 No.94-M91, CSA C22.2 No.142-
M1987, CSA C22.2 157-92, CAN/CSA C22.2 No. 60529:05,
ANSI/ISA 12.27.01-2003
Markings
CL I, DIV 1, GP A, B, C, D, T4 see installation drawing
9240030-937; Non-Incendive Class III, DIV 1, Haz-loc CL I DIV 2,
GP A, B, C, D, Maximum Ambient Temperature +60 °C, T4, Type
4X/IP66/IP67, Maximum Working Pressure 5000 psi, Dual Seal.
Ui Ii Pi Ci Li
FISCO parameters 17.5 V 380 mA 5.32 W 0 0
9.7 Europe
9.7.1 E1 ATEX Flameproof
Certificate
Nemko 04ATEX1073X
Standards
EN 60079-0:2012, EN 60079-1:2014, EN 60079-11:2012, EN
60079-26:2015, EN 60079-31:2014
Markings
II 1/2G Ex db ia IIC T4 Ga/Gb, (-40 °C ≤ Ta ≤ +60 °C /+70 °C)
II 1D Ex ta IIIC T69 °C/T79 °C Da, (-40 °C ≤ Ta ≤ +60 °C /+70
°C)
Um = 250 V
Special Conditions for Safe Use (X):
1. Potential ignition hazards by impact or friction need to be considered
according to EN 60079-0:2012 clause 8.3 (for EPL Ga and EPG Gb), and
clause 8.4 (for EPL Da and EPL Db), when the transmitter enclosure and
antennas exposed to the exterior atmosphere of the tank, is made
with light metals containing aluminium or titanium. The end user shall
determine the suitability with regard to avoid hazards from impact and
friction.