Standards
EN 60079-0:2012, EN 60079-11:2012, EN 60079-15:2010, EN
60079-31:2014
Markings
II 3G Ex nA ic IIC T4 Gc (-50 °C ≤ Ta ≤ +60 °C /+70 °C)
II 3G Ex ic IIC T4 Gc (-50 °C ≤ Ta ≤ +60 °C /+70 °C)
II 3D Ex tc IIIC T69 °C/T79 °C Dc (-50 °C ≤ Ta ≤ +60 °C /+70 °C)
Special Conditions for Safe Use (X):
1. The transmitter circuits does not withstand 500V AC dielectric
strength test according to EN 60079-11 clause 6.3.13 due to earth
connected transient suppressing devices. Appropriate measures have
to be considered by installation.
Ui Ii Pi Ci Li
Safety parameters
HART
42.4 V 23 mA 1 W 7.25 nF Negligible
Safety parameters
Fieldbus
32 V 21 mA 0.7 W 4.95 nF Negligible
9.8 International
9.8.1 E7 IECEx Flameproof
Certificate
IECEx NEM 06.0001X
Standards
IEC 60079-0:2011, IEC 60079-1:2014-06, IEC 60079-11:2011;
IEC 60079-26:2014, IEC 60079-31:2013
Markings
Ex db ia IIC T4 Ga/Gb (-40 °C ≤ Ta ≤ +60 °C /+70 °C)
Ex ta IIIC T69 °C/T79 °C Da (-40 °C ≤ Ta ≤ +60 °C /+70 °C)
Um=250 VAC, IP66/IP67
Special Conditions for Safe Use (X):
1. Potential ignition hazards by impact or friction need to be considered
according to IEC 60079-0:2011 clause 8.3 (for EPL Ga and EPL Gb) and
clause 8.4 (for EPL Da and EPL Db), when the transmitter enclosure and
antenna exposed to the exterior atmosphere of the tank, is made with
light metals containing aluminum or titanium. The end user shall
determine the suitability with regard to avoid hazards from impact and
friction.
2. Parts of the sensor probes for the type 5300 are non-conducting and
the area of the non-conducting part exceeds the maximum
permissible areas for Group III according to IEC 60079-0.2011 clause
7.4:3 Therefore, when the antenna is used in a potentially explosive
February 2019 Quick Start Guide
Quick Start Guide 35