Ex tc IIIC T69 °C/T79 °C Dc (-50 °C ≤ Ta ≤ +60 °C /+70 °C)
Special Conditions for Safe Use (X):
1. The transmitter circuits does not withstand 500V AC dielectric
strength test according to EN 60079-11 clause 6.3.13 due to earth
connected transient suppressing devices. Appropriate measures have
to be considered by installation.
Ui Ii Pi Ci Li
Safety parameters
HART
42.4 V 23 mA 1 W 7.25 nF Negligible
Safety parameters
Fieldbus
32 V 21 mA 0.7 W 4.95 nF Negligible
9.9 Brazil
9.9.1 E2 INMETRO Flameproof
Certificate
UL-BR 17.0188X
Standards
ABNT NBR IEC 60079-0:2013, ABNT NBR IEC 60079-1:2016,
ABNT NBR IEC 60079-11:2013, ABNT NBR IEC 60079-26:2016,
ABNT NBR IEC 60079-31:2014
Markings
Ex db ia IIC T4 Ga/Gb (-40 °C ≤ T
amb
≤ +60 °C /+70 °C)
Ex ta IIIC T69 °C/T79 °C Da (-40 °C ≤ T
amb
≤ +60 °C /+70 °C)
Um=250 V
ac
, IP66/67
Special Conditions for Safe Use (X):
1. See certificate for Specific Conditions.
9.9.2 I2 INMETRO Intrinsic Safety
Certificate
Certificate: UL-BR 17.0188X
Standards
ABNT NBR IEC 60079-0:2013 , ABNT NBR IEC 60079-11:2013,
ABNT NBR IEC 60079-26:2016, ABNT NBR IEC 60079-31:2014
Markings
Ex ia IIC T4 Ga (- 55 °C ≤ T
amb
≤ +60 °C /+70 °C)
Ex ia IIIC T69 °C/T79 °C Da (- 50 °C ≤ T
amb
≤ +60 °C /+70 °C)
Special Conditions for Safe Use (X):
1. See certificate for Specific Conditions.