Connect to device using a handheld communicator
Procedure
Turn on the handheld communicator and connect to the device.
Configure HART
®
devices
Procedure
1. Select Configure Guided Setup.
2. Select Level Measurement Setup and follow the instructions.
3. Select Device Specific Setup.
4. Run Verify Level to check your level measurement.
5. (Optional) Select Volume Setup.
6. (Optional) Select Display Setup.
2.4.3
Damping
User adjusted damping will affect the transmitter’s ability to respond to process changes.
Therefore, the damping values + response time should not exceed the loop requirements.
For further information on damping, see Reference Manual.
2.4.4
Write protection
A Rosemount 5300 Level Transmitter safety-certified transmitter should always be
protected from unintentional configuration changes by a password protected function. It
is recommended to use write protection described in Reference Manual.
2.4.5
Alarm and saturation levels
DCS or safety logic solver should be configured to handle both High alarm and Low alarm.
In addition, the transmitter must be configured for High or Low alarm.
Note
In certain cases, the transmitter does not go into the user defined alarm state. For
example, in case of a short circuit, the transmitter goes into High Alarm state even if Low
Alarm has been configured.
Figure 2-2 identifies the alarm levels available and their operation values.
Installation and commissioning Safety Manual
September 2020 00809-1900-4530