EasyManua.ls Logo

Emerson SolaHD SDU DC UPS B Series - Battery Module Specifications

Emerson SolaHD SDU DC UPS B Series
23 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page: 17
Table 10
Battery Module Specifications
Parameter
Catalog Number
SDU 24-BATB SDU 24-BATEM
Nominal Voltage 24 V dc
Protection Fuse: 30 A Circuit Breaker: 24 V, 25 A
Charging Current 1.2 A
Battery Type Sealed, maintenance-free lead acid batteries
Enclosure Type IP20 NEMA 1
Terminal Connector Type Polarized power pole connectors
Operating Temperature -15°C to +50°C
Storage Temperature -15°C to +40°C
Humidity 95%, non-condensing
Typical Recharge Time
(to 90% of full capacity)
SDU 24-BATB: 6 hours for 2 battery modules; 3 hours for each additional
battery module SDU 24-BATEM: 8 hours for 1 battery module
Backup Times See Tables 5–8
Weight 11.46 lb. (5.2 kg) 16 lb. (7.26 kg)
Enclosure Dimensions
7.57 in. x 4.85 in. x 4.33 in.
(192.4 mm x 123.3 mm x 110 mm)
11.50 in. x 5.57 in. x 4.57 in.
(292 mm x 142 mm x 116 mm)
Mounting
Simple snap-on system for DIN rail
TS35/7.5 or TS35/15 or optional
chassis mounting brackets
(P/N: SDU-PMBRK)
Chassis mounting brackets
(P/N: SDU-PMBRK)
Accessories
1 ft (30.5cm) polarized
battery cable
6 ft (180cm) polarized
battery cable
*The SDU DC UPS B-Series system includes a power module (SDU 10-24B or SDU 20-24B)
and a battery module (SDU 24-BATB or SDU 24-BATEM).