Storage
Extended Storage
• Store the UPS covered and upright in a cool, dry location with the battery fully charged.
• Remove the REMOTE ON/OFF Bypass Jumper (or turn remote ON/OFF Switch to OFF position). Remove
any accessories in the accessory slot and disconnect any cables connected to the computer interface
port to avoid unnecessary draining of the battery.
• During extended storage in environments where the ambient temperature is -15°C to +30°C (+5°F to
+86°F), charge the UPS battery every 4 months.
• During extended storage in environments where the ambient temperature is +30°C to +45°C (+86°F to
+113°F), charge the UPS battery every three (3) months.