Unidrive M700/M701 / Unidrive HS70/HS71 Control Getting Started Guide 41
Issue Number: 2
Safety information Introduction Control connections Getting started
Basic parameters 
(Menu 0)
Running the motor
Further information
6.2.4 RFC-S mode (with position feedback)
Permanent magnet motor with a position feedback 
For simplicity only an incremental quadrature encoder with commutation outputs will be considered 
here. For information on setting up one of the other supported speed feedback devices, refer to 
Setting up a feedback device in the Drive User Guide.
Action Detail
Before 
power-up
Ensure:
• The drive enable signal is not given (terminal 31)
• Run signal is not given
• Motor and feedback device are connected
Power-up the 
drive
Verify that RFC-S mode is displayed as the drive powers up. If the mode 
is incorrect see section 4.7 Changing the operating mode on page 20
Ensure: 
Drive displays ‘inhibit’ 
Set motor 
feedback 
parameters
Incremental encoder basic set-up
Enter:
• Drive encoder type in Pr. 03.038 = AB Servo  (3): Quadrature 
encoder with commutation outputs
• Encoder power supply in Pr. 03.036 = 5 V (0), 8 V (1) or 15 V (2).  
• Drive encoder Pulses Per Revolution in Pr 03.034 (set according to 
encoder)
• Drive encoder termination resistor setting in Pr 03.039:
0 = A-A\, B-B\, Z-Z\ termination resistors disabled
1 = A-A\, B-B\, termination resistors enabled, Z-Z\ termination 
resistors disabled
2 = A-A\, B-B\, Z-Z\ termination resistors enabled 
Motor 
thermistor 
set-up
At factory default, terminal 8 is set-up for an analog voltage input. If a 
thermistor is connected to terminal 8, then the Analog Input 3 Mode 
(07.015) parameter must be set to Thermistor Short Cct (7), Thermistor 
(8) or Therm No Trip (9). 
Enter motor 
nameplate 
details
Enter:
• Motor rated current in Pr 00.046 (A)
Ensure that this equal to or less than the Heavy Duty rating of the 
drive otherwise ‘Motor Too Hot’ trips may occur during the autotune.
• Number of poles in Pr 00.042
• Motor rated voltage in Pr 00.044 (V) 
Set 
maximum 
speed
Enter:
• Maximum speed in Pr 00.002 (rpm)
If output voltage from the encoder is >5 V, then the termination 
resistors must be disabled Pr 03.039 to 0. 
Setting the encoder voltage supply too high for the encoder 
could result in damage to the feedback device
The thermistor input will be disabled until Pr 07.015 is set to 
one of the above.
Model No: 95UXXXXXXXXXXXX
Volts:   380/480
Cont:   7.7Nm: 4.81Arms
Stall:    9.5Nm:5. 91Arms
Speed: 3000rpm Poles:6
Kt:       1.6Nm/Arms
Ins Class: H
Brake: 12Nm
24V
0.67A
Serial No: XXXXXXXXXXX
Control Techniq ues
Dynamics Ltd
ANDOVER, HANTS.
ENGLAND. SP10 5AB