Unidrive M700/M701 / Unidrive HS70/HS71 Control Getting Started Guide 15
Issue Number: 2
Safety information Introduction Control connections
Getting started
Basic parameters 
(Menu 0)
Running the motor Further information
4. Select 'Save parameters in drive' to perform a parameter save.
The drive is now ready to run.
Action Detail
Motor Setup
Unidrive M Connect contains a database for induction motors and permanent magnet motors. 
Provision is also made to enter motor nameplate data.
The next section describes the use of the motor database for a Leroy Somer LSRPM motor 
used in RFC-S Sensorless mode.
Motor Feedback 
Setup
This only needs to be performed in RFC-A (with feedback) mode 
Set Pr 03.024 = Feedback (0)
Enter:
• Encoder power supply in Pr. 03.036 = 5 V (0), 8 V (1) or 15 V (2). *
 If output voltage from the encoder is >5 V, then the termination resistors must be 
disabled Pr 03.039 to 0. *
• Drive encoder Lines Per Revolution (LPR) in Pr 03.034 (set according to encoder) *
• Drive encoder termination resistor setting in Pr 03.039: *
0 = A-A\, B-B\ termination resistors disabled
1 = A-A\, B-B\, termination resistors enabled
* mm is dependant on the slot into which the SI-Encoder module is installed (15 =Slot 1, 16 = 
Slot 2, 17 = Slot 3). 
Analog I/O
The motor thermistor can be selected in Pr 07.015. Refer to the parameter help for Pr 07.015 
for further information.
Ramps Setup
Enter the required Acceleration rate and Deceleration rate
Note: If a braking resistor is installed, set 'Ramp mode' to 'Fast'. Also ensure Pr 10.030 and 
Pr 10.031 and Pr 10.061 are set correctly, otherwise premature 'Brake R Too Hot' trips may 
be seen).
Autotune
Not required when using data from the motor database for a Leroy Somer LSRPM motor used 
in RFC-S Sensorless mode.
Setting the encoder voltage supply too high for the encoder could result in 
damage to the feedback device.