38 Unidrive M700/M701 / Unidrive HS70/HS71 Control Getting Started Guide
Issue Number: 2
Autotune
The drive is able to perform either a stationary or a rotating autotune.
The motor must be at a standstill before an autotune is enabled. A
stationary autotune will give moderate performance whereas a rotating
autotune will give improved performance as it measures the actual
values of the motor parameters required by the drive.
To perform an autotune:
•Set Pr 00.040 = 1 for a stationary autotune or set Pr 00.040 = 2 for a
rotating autotune
Close the drive enable signal (terminal 31). The drive will display
’Ready’.
Close the run signal (terminal 26 or 27). The lower display will flash
‘Autotune’ while the drive is performing the autotune.
Wait for the drive to display ’Ready’ or ‘Inhibit’ and for the motor to
come to a standstill
Remove the drive enable and run signal from the drive.
Save
parameters
Select 'Save Parameters' in Pr
mm.000
(alternatively enter a value of
1000 in Pr
mm.000
) and press red reset button or toggle the reset
digital input.
Run Drive is now ready to run
Action Detail
A rotating autotune will cause the motor to accelerate up to
2
/
3
base speed in the direction selected regardless of the
reference provided. Once complete the motor will coast to a
stop. The enable signal must be removed before the drive
can be made to run at the required reference.
WARNING
cos
σ
L
S
T
Nm
N rpm
saturation
break-
points
R
S
L
S
Unidrive M700_M701 Getting Started Guide English iss7.book Page 38 Friday, December 12, 2014 1:14 PM