Emotron AB 01-3990-11r3 Software index 67
Notes:
1. To switch to Run/Stop with Function 1-01 = 0001.
2. To switch to Forward/Reverse with Function 1-01 = 0001.
3. Preset Speed #3 is obtained by activating Terms. S3 and S4 simultaneously.
5-08
Stop Mode
Using MFIT
0000: When the MFITs are
Programmed for Up/Down Frequency
Control, the Set Frequency will remain
when the Drive stops. And when the
Drive stops, Up/Down Function is
disabled.
0001: Up/Down is used. The preset
frequency is reset to 0 Hz as the VSD
stops.
0002: When the MFITs are
Programmed for Up/Down Frequency
Control, the Set Frequency will remain
when the Drive stops. And when the
Drive stops, Up/Down Function is
enabled. *7
0000
5-09
Step of Up/
Down
Function (Hz)
0.00 to 5.00 0.00
5-10
Encoder
Impulse Ratio
0.001 to 9.999 1.000 V2.3
5-11
Switch the
source of fre-
quency com-
mand
0=refer to 6-00
1= VR on keypad
2=AIN on control terminal TM2
3=Up/Down on TM2
4= reference via serial communication
0V2.3
5-12
AI2 function
selection
0020 PID feedback
0021 Bias Signal 1 input
0022 Bias Signal 2 input
0020
Function
Code no.
Description Range/Code
Factory
setting
Re-
marks