70 Software index Emotron AB 01-3990-11r3
9- Drive and Load Protection Modes
Function
Code no.
Description Range/Code
Factory
setting
Re-
marks
9-00
Trip Prevention
Selection During
Acceleration
0000: Enable Trip Prevention
During Acceleration
0001: Disable Trip Prevention
During Acceleration
0000
9-01
Trip Prevention Level
During Acceleration
(%)
50 to 300 200
9-02
Trip Prevention
Selection During
Deceleration
0000: Enable Trip Prevention
During Deceleration
0001: Disable Trip Prevention
During Deceleration
0000
9-03
Trip Prevention Level
During Deceleration
(%)
50 to 300 200
9-04
Trip Prevention
Selection in Run
Mode
0000: Enable Trip Prevention in
Run Mode
0001: Disable Trip Prevention in
Run Mode
0000
9-05
Trip Prevention Level
In Run Mode (%)
50 to 300 200
9-06
Trip Prevention
Deceleration Time
Selection in Run
Mode
0000: Trip Prevention Deceleration
Time Set by 3-03
0001: Trip Prevention Deceleration
Time Set by 9-07
0000
9-07
Deceleration Time In
Trip Prevention Mode
(Seconds)
0.1 to 3600.0 3.0
9-08
Electronic Motor
Overload Protection
Operation Mode
0000: Enable Electronic Motor
Overload Protection
0001: Disable Electronic Motor
Overload Protection
0000