Emotron AB 01-3990-11r3 Software index 71
9-09 Motor Type Selection
0000: Electronic Motor Overload
Protection Set for Non-VSD Duty
Motor
0001: Electronic Motor Overload
Protection Set for VSD Duty Motor
0000
9-10
Motor Overload
Protection Curve
Selection
0000: Constant Torque (OL=103%)
(150% for 1 Minute)
0001: Variable Torque (OL=113%)
(123% for 1 Minute)
0000
9-11
Operation After
Overload Protection
is Activated
0000: Coast-to-Stop After Overload
Protection is Activated
0001: Drive Will Not Trip when
Overload Protection is Activated
(OL1)
0000
9-12
Over torque
Detection Selection
0000: Disable Over torque
Operation
0001: Enable Over torque
Operation Only if at Set Frequency
0002: Enable Over torque
Operation while the Drive is in Run
Mode
0000
9-13
Operation After Over
torque Detection is
Activated
0000: Drive will Continue to
Operate After Over torque is
Activated
0001: Coast-to-Stop After Over
torque is Activated
0000
9-14
Over torque
Threshold Level (%)
30 to 200 160
9-15
Over torque
Activation Delay Time
(s)
0.0 to 25.0 0.1
Function
Code no.
Description Range/Code
Factory
setting
Re-